Reported Concern: AC ran continuously in Sector 78 bedroom but blew only normal fan air on warm afternoon.
Technician Inspection: Pressure testing found micro-leakage at the brass flare connection on outdoor unit.
Repair Work Completed: Refabricated copper flare connection, vacuumed lines properly, and recharged measured R32 gas.
Parts: ₹1,800 (R32 Gas Recharge & Brass Flare)
•
Labour: ₹700 (Leak Fix & Vacuuming)
•
Total Estimate: ₹2,500
Grill supply air temperature dropped to 11.5°C with fast room cooling.
Reported Concern: Indoor unit turned on in Sector 62, but outdoor unit made a brief hum and failed to start compressor.
Technician Inspection: Tested dual capacitor; capacitance had dropped from 50µF down to 14µF from summer heat.
Repair Work Completed: Installed a heavy-duty dual motor run capacitor and inspected wiring connectors.
Parts: ₹450 (Heavy Duty Dual Capacitor)
•
Labour: ₹350 (Outdoor Servicing)
•
Total Estimate: ₹800
Outdoor compressor started instantly with smooth, balanced motor sound.
Reported Concern: Water overflowed from the indoor plastic body in Sector 137, wetting the painted bedroom wall.
Technician Inspection: Dust sludge and mold had choked the internal drain tray outlet hole.
Repair Work Completed: Flushed condensate drain pipe with pressure and cleared the drain tray thoroughly.
Parts: ₹0 (Drain Clearing)
•
Labour: ₹400 (Indoor Drain Servicing)
•
Total Estimate: ₹400
Water flowed freely through the external drain hose with zero indoor overflow.
Reported Concern: AC produced a fluttering noise and weak airflow in Sector 50 even at maximum fan speed.
Technician Inspection: Sticky dust had accumulated on the curved fins of the cross-flow blower roller.
Repair Work Completed: Washed blower wheel using high-pressure jet pump with protective service apron jacket.
Parts: ₹0 (Deep Foam Wash)
•
Labour: ₹650 (Jet Servicing)
•
Total Estimate: ₹650
Airflow velocity doubled and fan noise dropped to whisper quiet.
Reported Concern: AC cooled for only 5 minutes before shutting compressor off, leaving room humid.
Technician Inspection: Indoor copper tube sensor had drifted, sending wrong cooling signals to the control board.
Repair Work Completed: Replaced the dual indoor sensor harness (room air + coil sensor) and verified cycle time.
Parts: ₹380 (Dual Sensor Harness)
•
Labour: ₹400 (Diagnosis & Replacement)
•
Total Estimate: ₹780
Compressor ran steady cooling cycles, maintaining accurate 24°C room temperature.
Reported Concern: Inverter split AC flashed communication fault code after a voltage fluctuation in Sector 93.
Technician Inspection: Signal coupler component on the outdoor inverter controller board was damaged by line surge.
Repair Work Completed: Replaced signal components on inverter board and checked supply earthing.
Parts: ₹450 (Board Components)
•
Labour: ₹750 (Inverter Board Repair)
•
Total Estimate: ₹1,200
Indoor and outdoor units synced within a minute; compressor cooled normally.